Abstract
The application of a high voltage capacitance bridge based on the current comparator to the measurement of the loss angle of high voltage shunt reactors is described. Measurements on three core-less 55 MVA, 735 kV single phase shunt reactors are discussed and a comparison is made with the results of a calorimetric determination of loss which indicates agreement to better than 2 percent. Other bridge techniques for this type of measurement are reviewed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.