Abstract
Sensors for measuring vertical current density at ground level near high voltage dc (HVDC) transmission lines are subject to error when the sensor is not in the ground plane. The magnitude of this error, for guarded and unguarded sensors, has been investigated using hoth dc electric fields with space charge and ac electric fields in a parallel plate facility. For conditions like those expected under HVDC transmission lines, the results obtained using ac and dc methods agreed to within experimental uncertainty. The measuired errors are as large as 25 percent for guarded sensors and significantly larger for unguarded sensors. Data for various sensor elevations and guarding are presented in graphs to aid the designer. Comparisons with results from an IEEE Working Group field day are also presented.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.