Abstract
The accurate measurement of inrush current is a key problem in transformer protection. Traditional electromagnetic current transformer (CT) has nonlinear characteristics of its core. When the transformer generates inrush current, it will be saturated and lead to current distortion, which will lead to transformer differential protection misoperation. Optical current transducer (OCT) is not affected by saturation and can be used to measure and identify inrush current well. This paper analyses the mechanism of inrush current, the reason of CT saturation and the principle of OCT measurement. The simulation and experimental results show that OCT has better measurement quality than traditional CT and superiority to differential protection.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.