Abstract

The authors compared serum beta-methyldigoxin (MDx) levels in digitalized patients by enzyme immunoassay (EIA) using anti-MDx 3'-hemisuccinate BSA antiserum (antiserum-I) with commercial antidigoxin antiserum (antiserum-II). The usefulness of a phenyl boric acid (PBA) column for pretreatment of the serum samples was also investigated. The assay using antiserum-I demonstrated good accuracy and precision in the concentration range of 0.5 to 5 ng/mL. When the specificities of antiserum-I and antiserum-II were assessed by cross-reactivity studies with various related compounds, antiserum-I was much more specific for MDx antiserum-II. Using a phenyl boric acid (PBA) column, MDx, and digoxigenin, which exhibits a negligible cross-reactivity, were separated from serum, including MDx and its metabolites. The recovery tests of MDx using antiserum-I with a PBA column in human serum were satisfactory and no interference of metabolites of MDx was observed. Mean MDx concentrations in serum samples (n = 30) from digitalized patients by EIA using antiserum-I with PBA column, antiserum-I, and antiserum-II were 1.06, 1.30, and 1.74 ng/mL, respectively. These results indicate that our EIA system using antiserum-I with a PBA column for pretreatment of serum samples is useful to more precisely measure the unchanged type of MDx in patients.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call