Abstract

In a raised floor data center, cold air from a pressurized subfloor plenum reaches the data center room space through perforated floor tiles. Presently, commercial tool “Flow Hood” is used to measure the tile air flow rate. Here, we will discuss the operating principle and the shortcomings of the commercial tool and introduce two other tile air flow rate measurement tools. The first tool has an array of thermal anemometers (named as “Anemometric Tool”), and the second tool uses the principle of temperature rise across a known heat load to measure the tile air flow rate (named as “Calorimetric Tool”). The performance of the tools is discussed for different types of tiles for a wide range of tile air flow rates. It is found that the proposed tools result in lower uncertainty and work better for high porosity tiles, as compared to the commercial tool.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.