Abstract
Advanced adiabatic compressed air energy storage (AA-CAES) could play an important role in power distribution system for mitigating the intermittency of distributed renewable generations and reducing the peak-valley difference of load demand, which requires to operate AA-CAES under off-design conditions. A power system dispatch oriented AA-CAES model was proposed based on the technically thermodynamic performance curves of compressor and expansion calibrated from experiments, highlighting the impact of AA-CAES part-lard features on charging/discharging efficiency and capacity. The proposed model is integrated with economic dispatch problem of power distribution systems, giving rise to a nonlinear program due to the state-dependent charging and discharging performances. The dispatch model is further linearized via piecewise linear approximation and special-ordered set of type 2, and its equivalent mixed integer linear formulation is presented. A modified IEEE 33-bus system is adopted to verify the effectiveness of proposed model for renewables accommodation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.