Abstract

Appendix A of ANSI/ASHRAE Standard 62.1-2007, Ventilation for Acceptable Indoor Air Quality, describes the recycling of unvitiated ventilation air in a recirculating air-handling system. Equation A-2 considers air delivered through the primary air path (central air distribution system) and secondary air paths, such as fan-powered boxes or transfer-air fans. It contains a variable, Er , that describes the extent to which the secondary air comes from the zone in question, as opposed to coming from “average system return air.” This paper describes the development of an equation that can be used to quantify Er , and shows the results of the first experimental measurements of Er . For these measurements, tracer gas experiments were carried out on an office building in Omaha, Nebraska. The study showed that the theoretical range of Er is from zero to infinity. Its range in the test building is from 0.74 to 1.01 as built, but could range from 0.14 to 1.13 if the fan-powered boxes had been located in different, but realistic, locations. These findings contradict the standard, which defines Er as ranging from 0 to 1.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.