Abstract

The deployment of inexpensive thyristor/triac controllers improve the efficiency and do not increase the power factor of induction motors (as measured at the input of pole transformer) operating under variable torque and constant speed constraints. Computer-aided testing yields detailed input/output powers for the drive. The improvement of the power factor does not increase the real-power capability (RPC) of a transformer supplying power to such drives due to current harmonics. Although the total harmonic current distortion (THDi) may exceed IEEE 519 and IEC 555 recommendations, recent publications show that the impact on the apparent power derating of a 25 kVA pole transformer is small if the THDi is less than 50%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.