Abstract
Air infiltration and ventilation rate measurements were made during all seasons of the year in eight federal office buildings using an automatic air infiltration system designed at the National Bureau of Standards. The eight federal office buildings were located in Anchorage, Alaska; Ann Arbor, Michigan; Columbia, South Carolina; Fayetteville, Arkansas; Huron, South Dakota; Norfolk, Virginia; Pittsfield, Massachusetts; and Springfield, Massachusetts. These buildings ranged in size from 1730 m2 (18 600 ft2) for the building in Pittsfield to 45 500 m2 (490 000 ft2) for the Anchorage federal building. All were constructed within the last 10 years. Air infiltration rates were found to vary from 0.2 to 0.7 air changes per hour and constituted from 23% to 61% of the building design load. Minimum ventilation rates in the tighter buildings were found to be less than what would be recommended for occupied offices.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.