Abstract

The paper discusses the implications of the increasing capacity of synchronous generators at the remote ends of rural distribution networks where the line resistances are high and the X/R ratios are low. Local voltage variation is specifically examined and two methods of compensation are proposed. The first of them is a deterministic system that uses a set of rules to switch intelligently between voltage and power factor control modes, while the second is based on a fuzzy inference system that adjusts the reference setting of the automatic power factor controller in response to the terminal voltage. Extensive simulations have verified that the proposed approaches may increase the export of real power while maintaining voltage within the statutory limits.