Abstract

The paper analyses the existing calculation methods for steam turbine condenser. The refined methods for calculating the condenser have also been considered. The dependency of the vapor pressure in the condenser on the temperature of the cooling water and the steam flow rate into the condenser have been considered. It can be seen from the obtained dependencies that the calculation of the condenser according to the ARTI and HEI (USA) methods coincides with the passport data. It is recommended to use the ARTI and HEI (USA) techniques for equipment diagnostics, and to use the KTP and USTU-UPI techniques when studying ways to increase the efficiency of the condenser. The mathematical model of the KG2-6200 condenser has been tested at the Almaty СHPP-2.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.