Abstract

OF THESIS MATHEMATICAL MODEL FOR CURRENT TRANSFORMER BASED ON JILESATHERTON THEORY AND SATURATION DETECTION METHOD Current transformer saturation will cause the secondary current distortion. When saturation occurs, the secondary current will not be linearly proportional to the primary current, which may lead to maloperation of protection devices. This thesis researches and tests two detecting methods: Fast Fourier Transform (FFT) and Wavelet Transform based methods. Comparing these two methods, FFT has a better performance in steady state saturation, and Wavelet Transform can determine singularity to provide the moment of distortion. The Jiles-Atherton (J-A) theory of ferromagnetic hysteresis is one approach used in electromagnetics transient modeling. With decades of development, the J-A model has evolved into different versions. The author summarizes the different models and implements J-A model in both MATLAB and Simulink.