Abstract

Flooded lead-acid battery dominates the emergency power supply system of nuclear power plants. However, Valve-Regulated Lead-Acid (VRLA) battery occupies important parts in emergency power supply systems. Structure design for internal consistency of big capacity is a challenge. Electrical variables of battery fluctuate as hysteresis while aging. This paper decouples terminal voltage in deep discharge by concentration polarization of electrolyte. Voltages of both bulk electrolyte capacitance and internal resistance are constants. This principle presents a novel model of dynamic threshold of contacting resistance. The model is sensitive to the battery nonlinear hysteresis. The model alarms remaining useful capacity at the end of service life. Parallel experiments at 4200 (Ah) VRLA batteries verifies the model. A Microchip embedded management board runs the algorithm.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.