Abstract

Arcing faults on low-voltage insulated conductors are widely considered to be self-extinguishing and consequently not very hazardous to people or property. Nevertheless, a number of arcing faults recently occurred on Hydro-Quebec's underground secondary 120/240 V and 347/600 V systems and caused manhole explosions in downtown Montreal. To trace the probable cause, a series of staged tests was performed in IREQ's high-power laboratory. The results obtained proved that in wet, dirty ducts an arcing fault can take the form of an interrupted arc which is difficult if not impossible for common overcurrent protection systems to detect. Any such fault that has a long duration produces a significant amount of gaseous by-products which escape to the ends of the duct where they can ignite or form explosive concentrations. >

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.