Abstract

The residual chlorine in chlorine-disinfected and dechlorinated wastewater was characterized using a liquid chromatograph that was switched between reversed-phase separation and flow injection analysis modes, permitting measurement of fractionated and total residual chlorine, respectively. Residuals were detected in the effluent of an operating wastewater treatment plant employing chlorine disinfection and sulfite dechlorination. Despite dechlorination, an estimated total residual chlorine of 3 μM (0.2 ppm as Cl 2) was detected in the effluent. To improve dechlorination effectiveness, four alternative agents (ascorbic acid, iron, sulfite plus iodide mediator, thiosulfate) were compared to sulfite on laboratory-chlorinated wastewater. Listed in order of decreasing relative effectiveness, we found: iron metal ≫ sulfite plus iodide ≈ thiosulfate > sulfite ≫ ascorbic acid. Only the iron metal column was completely effective at rapidly removing all traces of residual chlorine.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.