Abstract
The contact structure of the interrupter for the DC vacuum circuit breaker (VCB) is proposed in this paper. Based on the different structure, magnetic properties of the transverse magnetic field (TMF) and axial magnetic field (AMF) contacts, a hybrid AMF-TMF cup shape contact is presented. The steady magnetic field and the residual magnetic field has been analyzed using the finite element method (FEM). From the simulation results, it can be seen that: for the cognition of steady magnetic field, the middle region TMF of the hybrid AMF-TMF cup shape contact is enhanced, and the AMF in the central region is increased significantly. The RMF value for the novel hybrid cup is much smaller than that of the traditional cup, which is more favorable for the metal vapor diffusion and effective dissipation of the arc energy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.