Abstract
This paper proposes an N-step ahead model predictive controller for a multilevel asymmetric cascade grid-connected inverter. To this goal, a predictive function controller has been designed based on the Lyapunov theory. First, the equations of the N-step ahead predictive sequence have been derived for the reference current as well as the reference voltage using first-order linear interpolation considering the mean of previous values. Second, the current, voltage, current error, and Lyapunov function have been calculated for the N-samples ahead. Then, the switching scenario has been determined such that it minimizes the derivation of the Lyapunov function. Moreover, the effect of the number of prediction steps on the unwanted harmonic reduction, switching average, grid power injection, and inverter efficiency has been investigated. Finally, The proposed controller is implemented on a 19-level asymmetric cascaded inverter. The results show that by increasing the prediction steps from 1 to 5, the harmonic distortion and the number of switches are reduced.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical Power & Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.