Abstract
Chillers are widely used for cooling buildings in the subtropical regions at the expense of considerable energy. This paper discusses how the number and size of air-cooled chillers in a chiller plant should be designed to improve their energy performance. Using an experimentally verified chiller model, four design options were studied for a chiller plant handling the cooling load profile of an office building. Using chillers of different sizes is desirable to increase the number of steps of total cooling capacity. This enables the chillers to operate frequently at or near full load to save chiller power. Pumping energy can also be saved because of the improved control of chilled water flow whereby the chilled water supplied by the staged chillers can match with that required by air side equipment for most of the operating time. It is estimated that the annual electricity consumption of chiller plants could drop by 9.4% with the use of unequally sized chillers. The findings of this research will offer guidance on how to select chillers of different sizes for a low-energy chiller plant.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.