Abstract
Pumped storage units bring stability to the electrical power system, so they must remain connected to the grid even during grid faults. In this paper, the authors propose efficient and simple solutions for a doubly fed induction machine pumped storage (DFIMPS) system during grid faults. In case of balanced grid faults, a control reconfiguration strategy is introduced and a hardware solution is applied in the case of unbalanced grid faults. The reconfiguration strategy consists of a commutation between different control strategies; when a balanced grid voltage fault occurs during pumping mode, the control algorithm switches to the synchronization one but based on the new grid conditions. So the proposed reconfiguration method reduces the negative impacts of grid fault occurrence on the DFIMPS system by cancelling rotor and stator over-currents and decreasing the electromagnetic torque and stator power oscillations. Simulation results carried out on a 4 kW DFIMPS system illustrate the effectiveness of the proposed approach.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.