Abstract

This article deals with temperature-rise of current path of modern low-voltage circuit-breaker with rotary contact system at overloads and subsequent experimental verification of selected model. The first part describes optimal setting of input conditions of simulation and mainly transient phenomena at contacts causing dynamic change of contact resistances due to change of total contact force, a new challenge to be solved in this contribution. The second part devotes laboratory measurement on prepared sample of the breaker for verification of transient simulation. These simulations are not only important for understanding of rotary system behavior under overloads, but forms an essential part of R & D process due to the speed-up of optimal current path design. In the end, both the financial costs and time effort could be decreased.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.