Abstract

A network of three-channel low-temperature infrared-optical gas analyzers with a response time of 1 s is developed for detecting explosive and fire hazardous concentrations of gasified liquefied natural gas (LNG) at temperatures up to 150 K. Their characteristics are described in an analysis of its large-scale emissions into the atmosphere. It is shown that during pulsed LNG emissions in the form of submerged jets and spills on standard concrete and water, large-scale areas of mixtures of air, methane, and light alkane vapors form with an explosive concentration that fluctuates in time and volume. The evaporation of cryogenic methane droplets with diameters of more than 0.1 mm in air and methane vapor from temperatures T = 150–290 K has been studied theoretically and experimentally.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.