This paper discusses the fuel-oil portion of an evaluation, utilizing a multistaged combustion burner designed for in-furnace NOx control and high combustion efficiency, for high nitrogen-content fuel and waste-incineration application in a 0.6-MW package boiler simulator. A low-NOx precombustion chamber burner was reduced in size by about a factor of two (from 600 to 250 ms first-stage residence time) and coupled with (1) air staging, resulting in a three-stage configuration, and (2) natural gas fuel staging, yielding up to four stoichiometric zones. Natural gas, doped with ammonia to yield a 5.8% fuel nitrogen content, and distillate fuel oil, doped with pyridine to yield a 2% fuel nitrogen content, were used to simulate high nitrogen content fuel/waste mixtures. The multistaged burner reduced NO emissions by 85% from emission levels from a conventional unstaged burner mounted on a commercial package boiler. A minimum NO emission level of 110 ppm was achieved in the fuel-oil tests, from a level of 765 ppm for conventional firing.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.