Abstract

An investigation has been made to assess the performance of a conventional CCD camera, as commonly used in substation security schemes, for thermal imaging applications. CCD cameras are responsive to infrared radiation in the waveband 0.8-1.1 /spl mu/m. Software image averaging and filtering techniques were developed to improve the signal to noise ratio of the camera image. Laboratory tests conducted in the exclusion of light show that objects at temperatures as low as 280/spl deg/C can be reliably detected by a standard CCD camera. Although this temperature is probably too high for most power plant thermal monitoring, this work raises the question of whether camera resources for security and thermal investigations can be shared.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.