Abstract

The instability phenomena caused by converter–grid interactions can be prevented by designing controllers with adequate stability margins. Yet, the multiple-input–multiple-output (MIMO) dynamics of grid-connected voltage-source converters (VSCs) complicate the stability analysis for the controller design. To tackle this challenge, this article presents a loop-at-a-time stability analysis for grid-connected VSCs, which not only shows close correlations with the generalized Nyquist criterion for MIMO systems but also enables to quantify the stability margins of individual closed loops. Moreover, the interactions between the closed loops can be analyzed. Test cases with numerical sensitivity analysis, simulations, and field measurements of a converter validate the theory.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.