Abstract

In order to verify long-term reliability of amorphous alloy wound core distribution transformers, accelerated aging tests and field trials used on actual transformers were practised. As for accelerated aging tests, short-circuit tests were added to imitate mechanical stress in operation on a utility's distribution system. As a result, even after the equivalent of 30 years, which was the normal expected transformer's life, the magnetic characteristic was unchanged, so these transformers could be operated. Additionally, two hundred transformers of four kinds were installed on a utility's distribution system to study no-load characteristics. They were equipped with a mechanism to measure load current, background vibration and lightning surge current, so their influence on magnetic characteristic could be inspected. As a result, no remarkable change was seen even after six months.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.