Abstract

In order to investigate the current indoor air quality (IAQ) in China, we installed IAQ monitoring sensors in 117 homes. According to the results, only about 2% of homes were able to maintain an indoor PM2.5 concentration below 75 μg/m3 during the monitoring period, and 10% of homes were able to keep the nighttime carbon dioxide (CO2) concentration below 1000 ppm. In regard to the relationships between pollutant concentrations and outdoor environmental parameters, we found that when nighttime outdoor temperatures were between 10°C and 22°C, the CO2 concentrations essentially decreased as the temperature increased. In regard to the indoor/outdoor (I/O) ratios of PM2.5, the naturally ventilated homes had a median I/O ratio of around 0.88–0.97 when the outdoor PM2.5 concentration was lower than 75 μg/m3. The homes with portable air cleaners were able to maintain 89%, 71% and 56% of days with indoor PM2.5 concentrations lower than 25 μg/m3 in severe cold, cold and hot summer and cold winter zones, respectively. If we want to maintain both indoor CO2 and PM2.5 concentrations below guidelines (CO2: 1000 ppm, PM2.5: 25 μg/m3 ) for more than 95% of days during the whole year, the mechanical ventilation may be a good choice. But the efficiency of the particle filters in mechanical ventilation systems should be improved, with minimize efficiency of 86%, 85%, 74%, 58%, and 62% for severe cold, cold, hot summer and cold winter, moderate and hot summer and warm winter zones, respectively.