Abstract

High-stress design 35-kV ethylene propylene rubber (EPR)-insulated cables with 1.14-mm (45-mil) wall reduction have been in service for more than ten years. In the mid 1990s, an extensive cable testing program was initiated to demonstrate that high-stress designs up to 4 kV/mm (101.6 V/mil) exhibit a significant electrical and mechanical safety margin to operate on typical utility network systems. Investigations were also undertaken to demonstrate the suitability of accessories for high-stress designs. This paper will present the results of six-year, long-term wet electrical testing conducted to demonstrate that with proper design, the aging performance of standard wall and high-stress design cables provide satisfactory results and suitable performance for the intended application. Additionally, utility field experience is presented on 35- and 15-kV cables operating at high stress. The experience for these 15-kV medium-voltage EPR cable designs employ the highest recommended stress for cables of this class, as well as taking into account the complete system performance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.