Abstract
This paper describes the results of a performance review of a 10 kW/100 kWh commercial VFB system that has been commissioned and in operation for more than a decade. The evaluation focused on the system efficiencies, useable capacity, electrolyte stability and stack degradation. The analysis shows that the system has stable performance and very little capacity loss for over a decade since commissioning. Only very recently, a slight decrease in system discharge capacity (approximately 5 %) was observed and indicated by changes in the electrolyte valence state. The capacity was restored to the original level after conducting a rebalancing procedure. This demonstrates the advantage that the flow batteries employing vanadium chemistry have a very long cycle life. Furthermore, electrochemical impedance spectroscopy analysis was conducted on two of the battery stacks. Some degradation was observed in one of the stacks reflected by the increased charge transfer resistance. To further investigate the ageing of the stacks, reverse polarity tests were carried out. It is found that reversing the polarity both hydraulically and electrically can restore the stack performance. The study shows that the VFB is a reliable technology for large-scale energy storage applications.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.