Abstract

This paper presents the results of time to rupture tests on HV composite insulators with maximum tensile rupture loads in excess of 450 kN. Three insulator designs were evaluated and the results of tests at different temperatures are given. Based on the extrapolations of the more than 10 000 hours test results, the 50-year life rupture load is decreased to between 54 percent and 66 percent of the maximum rupture load depending on the insulator design.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.