Abstract

This study presents the results of a 3year experiment concerning the behavior of a geothermal ground-water heat pump used for heating a small residential house. The study is focused on the one side on the ground temperature variation around the horizontal collector oversized by ≈50%, mounted at 1.7m depth and on the other side on the working conditions and performances of the heat pump itself. It was highlighted that due to the oversizing of the geothermal collector, the ground temperature did not drop below 2°C and ground freezing was avoided. The ground temperature recovered each year during the non-heating season. The heat pump coefficient of performance was determined in the range of (3.18–8.59) in different operating periods.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.