Abstract

This study presents the results of a 3year experiment concerning the behavior of a geothermal ground-water heat pump used for heating a small residential house. The study is focused on the one side on the ground temperature variation around the horizontal collector oversized by ≈50%, mounted at 1.7m depth and on the other side on the working conditions and performances of the heat pump itself. It was highlighted that due to the oversizing of the geothermal collector, the ground temperature did not drop below 2°C and ground freezing was avoided. The ground temperature recovered each year during the non-heating season. The heat pump coefficient of performance was determined in the range of (3.18–8.59) in different operating periods.