Abstract
Concerning HV insulation in vacuum, there is still some uncertainty about the processes leading to breakdown, especially in the case of long time lags and large contact spacing. The present measurements show that mechanical shocks cause breakdown of the gap. Breakdown probability is highest for virgin contacts and decreases after heavy arcing. The role of nonmetallic inclusions and organic impurities is highlighted. In comparison with a demountable vacuum device industrial vacuum interrupters do not show any sensitivity to mechanical shocks. Besides breakdown probabilities and time lags, the temporal development of voltage and current during breakdown was measured. For a contact spacing of >14 mm and for breakdown sites located on the side face of the contacts, HV discharges were observed lasting for approximately 500 mu s. In this case, current is limited by a negative space charge layer in front of the anode.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.