Abstract

In this paper, three monitoring stages of detection, localization, and extent determination of radial deformation in power transformer winding using stationary ultra-wideband antennas, are investigated. For this purpose, two types of radial deformation are implemented on the actual transformer high-voltage winding. The first type is a modeled bulgy mechanical deformation, which its extent and reversibility may be changed and it can occur in different positions. The second type is an actual radial deformation applied to the winding. Hyperboloid method and 2-D locus of the winding are adopted in the localization stage. To perform a precise analysis of the received signals, matched filter technique is employed. The extent of the deformation is also determined by magnitude Euclidean distance index. The experimental results prove the effectiveness of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call