Abstract
This article describes the hybrid approach of the Firefly Algorithm and power-voltage curve method in optimal placement of Distributed Generation while considering the actual load model. The actual load model is represented by six models. The six load models are a composite of industrial, residential, and commercial loads with dissimilar percentages. The Institute of Electrical and Electronics Engineers 30 Bus is selected as the testing object for the proposed method. The optimal Distributed Generation placement process was performed using the Firefly Algorithm, while evaluation of optimal Distributed Generation on the loading and stability index is continued using the power-voltage curve method. The results show that commercial loads contribute to high power loss values. The optimal Distributed Generation integration results in an increase the stability index from 53.83% at initial conditions to 90.84% at maximum load level when increasing the maximum loading limit to 95%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.