Abstract

Abstract It is more dangerous for the units sharing the same division pipeline system than those sharing individual system during the load rejection transient for a high water head pumped storage station. A new mathematical model for the load rejection transient in these two units sharing the same division pipeline was proposed using method of internal characteristic (MIC). The transient relationship between the geometric parameters and working parameters was established based on the dynamic equations of the hydraulic machinery. Meanwhile, the calculation of the load rejection transient was accomplished and compared with field experimental data from a pumped storage power station. The relative errors of the maximum rotational speed of the two units between the predicted results and the experimental data were −5.9% and −4.44%, respectively, and the relative errors of the maximum rising of hydraulic pressure were −6.7% and −6.98%, respectively. The results met with the design specification requirements, which indicated that the proposed new MIC could completely predict the load rejection transient in these two units with joint closing law of ball-valve and guide vane, and the corresponding calculated results were acceptable and reliable. The MIC is also applicable to the transient investigation of hydraulic systems with hydraulic machinery.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.