Abstract

In this article, a load frequency control technique for an isolated small hydro power plant based on a multiple flow control system is proposed. In general, the frequency of the system is controlled by employing a dump load whose rating is equal to the rated power output of the plant. The proposed scheme reduces the size of the dump load to 50%, as 50% input power of the hydro plant is controlled by an on/off control. A generalized transfer function model for the system is developed with on/off control logic, and the parameters were optimized using the integral time absolute error technique. The on/off control linearly raises or lowers the generation. Finally, transient responses are shown for low, medium, and high head installations with different loading conditions.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call