Abstract

Application of current limiting protectors (CLPs) has been recommended in the existing literature to retain underrated medium voltage circuit breakers of lower short-circuit ratings in service, when the distribution systems are expanded and the short-circuit currents increase. However, the existing published literature does not describe the limitations of CLPs from system separation and loss of protective device coordination conditions, nor does it provide an analysis of short-circuit duties of medium voltage circuit breakers used with CLPs. The paper shows how these evaluations can be carried out. Considerations of high cost of replacements, the far greater loss of production due to lack of coordination and availability of a proven alternate solution should be included in an informed decision to use CLPs. 'CLP', 'triggered fault current limiter (TCL)', 'CLIP', and 'I/sub s/ Limiter' are synonymous.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.