Abstract

As a part of EPRI Research Project 2542-1, Characteristics of Lightning Surges on Distribution Lines, a coincident lightning events detector (CLED) was developed, tested, and installed in a test area on the Florida Power Company distribution system in St. Petersburg, Florida. The CLED provided the data to determine the number of lightning-caused circuit breaker operations for the first time. During the 3-year recording period, a total of 546 faults causing circuit breaker operations occurred on the seven circuits in the test area. Of these faults, 415 (or 76%) were temporary faults. A lightning strike was coincident with 42% of the temporary faults. Improper operation of line fuses was traced to the absence of lightning arresters at line fuse locations.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.