Abstract

Radio base stations (RBS) are composed of antenna systems on a steel tower, radio equipment systems on the ground, and interconnection signal/power cables. They are frequently exposed to lightning strikes. For protection against lightning, modeling such complex systems is always a necessary but tricky task. In this paper, a procedure is presented to model the RBS system. The steel structure that may carry substantial lightning currents during lightning strikes is included in the model. To facilitate time-domain simulations for frequency-dependent conductors, a vector fitting enhanced PEEC method is adopted. In this method, magnetic material, skin effect, and proximity effect are taken into account. Meanwhile, the models of protection circuits at the equipment ports are presented. Their circuit parameters are provided with the data collected from experiments. Laboratory tests on a simplified radio-base-station system are performed. Good agreements with the simulation results are observed. Finally, lightning surges in a practical RBS system are presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.