Abstract
This paper aims to compute the lightning electromagnetic transient overvoltage and current on the wind turbine using the PSCAD/EMTDC simulation program. The double-peaked lightning current, tower, grounding system models, and dangerous situation of the grounding system are investigated by the PSCAD simple circuit branch segment codes and defining components. A comparison analysis has been performed to see the influence of lightning current wave shapes and grounding characteristics. The simulation results show that 43 kA and 31 kA lightning currents produce 200 kV overvoltage on the turbine grounding in case of 1000 Ω·m soil resistivity. However, current amplitudes on the equipotential grounding system become 28 kA and 20 kA. The influencing factors of the surge protection device are determined using good accuracy computer simulation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.