This paper introduced the lightning protection design of the first 1000-kV UHV transmission line in China. The analysis is based on the lightning leader propagation model by considering the lightning propagation process, which can consider the randomness of lightning process. The new phenomenon of middle-phase shielding failure was explained when two grounding wires are wide, and the side-phase shielding failure characteristics of 1000-kV ac transmission line were presented also. The measures to improve the effect of lightning protection of this UHV line are discussed, and the application is presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.