Abstract

This paper deals with the assessment of the lightning performance of a medium voltage (MV) power line sharing the same poles of a high voltage (HV) line. We focus on the case of a 15-kV line with compact configuration that is supported by the concrete poles of a 69-kV or a 138-kV transmission line. Due to the taller HV pylons and conductors, the number of direct events to the multi-circuit line is higher than for a MV line alone. The presence of the HV conductors and of the overhead ground wire reduces the amplitudes of the induced overvoltages in the MV conductors due to indirect lightning events. For the considered configurations, with a compact MV line, the number of flashovers per year expected in the double-circuit line due to both direct and indirect flashes is lower than in a MV line alone. It is shown that such a number depends mainly on the line withstand voltage, on the grounding resistance and on the number of surge arresters. The dependence is quantitatively discussed in the paper. The analysis of the overvoltages transferred on the LV side of the distribution transformers is also performed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.