Abstract

17 years of lightning data from 1992 to 2008 obtained with lightning location system of 9 electric power companies in Japan have been summarized and analyzed. The recent annual number of lightning flashes of which current is more than 10 kA in Japan is around one million and the 50% value of cumulative distribution of lightning peak currents is about 20kA. The variation of lightning occurrence characteristics by areas, seasons and so on are clarified. The relationship between lightning occurrence and climate, detection efficiency and the version of lightning detection systems are discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.