Abstract

A modeling procedure that permits calculation of lightning-induced voltages on overhead lines starting from the channel-base current is discussed. The procedure makes use of a coupling model already presented in the literature, based on transmission line theory, for field-to-overhead line coupling calculations. Both models are discussed and compared with experimental results. The hypothesis of perfect conducting ground, used to analyze the voltages induced on an overhead line by a nearby lightning return stroke with a striking point equidistant from the line terminations, and the limits of its validity are determined. A comparison shows that peak value and maximum front steepness of the induced voltages calculated using other lightning return-stroke models differ. It is also shown that another coupling model used in the power-lightning literature by several other authors may result in a less accurate estimation of the induced voltages. >