Abstract

This paper deals with the calculation of lightning-induced overvoltages on medium-voltage (MV) and low-voltage (LV) distribution networks taking into account the presence of MV-LV distribution transformers and, in particular, the surge transfer through them. The influence of the high-frequency model adopted for the representation of the power transformer on the calculation results is analyzed, with regards to two different models, both identified and validated by means of laboratory measurements: namely, a simple pi of capacitances, and the more complex one introduced by Morched, Marti, and Ottevangers in 1993. Accurate simulation results provide information on the adequacy of both models for the calculations of interest. Additional results, useful to evaluate the expected level of power quality and the benefits achievable by a proper installation of protection devices, are presented making reference to a realistic and complex configuration of an overhead distribution system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.