Abstract

Li-ion batteries are expected to play a vital role in stabilizing the electrical grid as solar and wind generation capacity becomes increasingly integrated into the electric infrastructure. This article describes how two different commercial Li-ion batteries based on LiNi0.8Co0.15Al0.05O2 (NCA) and LiFePO4 (LFP) chemistries were tested under grid duty cycles recently developed for two specific grid services: (1) frequency regulation (FR) and (2) peak shaving (PS) with and without being subjected to electric vehicle (EV) drive cycles. The lifecycle comparison derived from the capacity, round-trip efficiency (RTE), resistance, charge/discharge energy, and total used energy of the two battery chemistries are discussed. The LFP chemistry shows better stability for the energy-intensive PS service, while the NCA chemistry is more conducive to the FR service under the operating regimes investigated. The results can be used as a guideline for selection, deployment, operation, and cost analyses of Li-ion batteries used for different applications.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.