Abstract

This paper describes the results of research on the effect of profile factor on leakage current of four types of 20kV-post insulators in dry and wet clean conditions. The high ac voltage applied to the post insulator during experiment was 25kV corresponding to the highest voltage on a 20kV system. The level of insulator wetting has been referred to the average daily rainfall data in Indonesia. Three common rainfall values have been considered, namely 20mm, 50mm and 100mm, which are equivalent to the amount of watering level of 16ml/s, 30ml/s, and 60ml/s respectively. The results showed the significant effect of profile factor on the level of leakage current of post insulator both in clean dry and wet conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.