Abstract
This paper reports a study on leakage current (LC) and trapped charge characteristics for contaminated glass insulator string. Four units of glass insulators recently removed from service were contaminated according to IEC 60507. The measurement of trapped charge distribution was made by a radially shaped stainless steel mesh surrounding each insulator while LC was measured using 100 Q shunt resistor. The results revealed that as the contamination levels increase, the amplitude of LC increases; but the amplitude of trapped charge decreases.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.