Laboratory tests were conducted to determine whether or not corrosion of lead cable sheath can, occur under cathodic protection conditions. Some of the runs were made in cells containing the aqueous solutions of chlorides or chlorides and alkali while other tests were made with the lead cable sheaths in contact with soil saturated with the various solutions. The results from all of these tests indicated that no corrosion of the cable sheath occurred in any of these environments so long as the cathode was receiving protective current. It was found, how-ever, that corrosion and pitting of lead cable sheath could occur when the protective current was interrupted. It was determined that the cathode products of previous cathodic protection constitute an environment for potentially serious corrosion at any time that the protective current ceases to flow to any part of the lead cable sheath. 5.2.1

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.