Abstract
The virtual rotor angle stability of interconnected multi-inverter power grids with virtual synchronous generator (VSG) model is studied under large disturbance. According to the VSG regulation scheme, its electromechanical dynamic model is derived. A Lyapunov like energy function candidate of the power system with VSG-controlled inverters is constructed to adopt the transient energy function method. After system large disturbances, the critical clearing times are obtained through potential energy boundary surface method and also verified through time-domain simulations. Furthermore, the impacts of virtual control parameters on system behaviours are also discussed and demonstrated through simulations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.