Abstract

We study the distributions of the resilience of power flow models against transmission line failures via a so-called backup capacity. We consider three ensembles of random networks, and in addition, the topology of the British transmission power grid. The three ensembles are Erdős–Rényi random graphs, Erdős–Rényi random graphs with a fixed number of links, and spatial networks where the nodes are embedded in a two-dimensional plane. We numerically investigate the probability density functions (pdfs) down to the tails to gain insight into very resilient and very vulnerable networks. This is achieved via large-deviation techniques, which allow us to study very rare values that occur with probability densities below 10−160. We find that the right tail of the pdfs towards larger backup capacities follows an exponential with a strong curvature. This is confirmed by the rate function, which approaches a limiting curve for increasing network sizes. Very resilient networks are basically characterized by a small diameter and a large power sign ratio. In addition, networks can be made typically more resilient by adding more links.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.